A serial based communications protocol designed for controlling lighting, specifically digitally controlled dimmable fluorescent ballasts. DALI requires the signals to be level shifted from VCC and GND to +9.5V - +25.5V and GND. The master component can addess up to 64 individual slaves & up to 16 groups.

Examples

DALI Master Example, reads the value of a keypad and sends out DALI commands based on the key pressed, 1 = switch on a slave's light, 2 = switch off a slave's light, 3 = read the slave's light level. FC6 Icon.png DALI Master Example1 DALI Slave Example, listens for DALI messages and checks that the group is correct before attempting to process the request and if required reply to the master. FC6 Icon.png DALI Slave Example1

Downloadable macro reference

ReceiveBackwardFrame

Attempts to receive an 8-bit reply

0 indicates timeout or no reply

Parameters

This macro has no parameters


Return value

BYTE


TransmitForwardFrame

Send out a 16-bit frame consisting of the 8-bit address and data bytes.

After sending the controller will attempt to receive

If a reply is detected then the Return value will equal to the reply.

If no reply is detected then the Return value will be 0.

Parameters

BYTE Address
Address byte
BYTE Data
Data Byte


Return value

BYTE


TransmitIndividualForwardFrame

Sends out an individual frame containing address and data.

After sending the controller will attempt to receive a reply.

If a reply is detected then the Return value will equal to the reply.

If no reply is detected then the Return value will be 0.

Parameters

BYTE Address
Individual Address 0-63
BYTE Type
0 = Data, 1 = Command
BYTE Data


Return value

BYTE


TransmitGroupForwardFrame

Sends out a group frame containing address and data.

After sending the controller will attempt to receive a reply.

If a reply is detected then the Return value will equal to the reply.

If no reply is detected then the Return value will be 0.

Parameters

BYTE Address
Group Address 0-15
BYTE Type
0 = Data, 1 = Command
BYTE Data


Return value

BYTE


Initialise

Configures the UART serial interface.

Parameters

This macro has no parameters


Return value

This call does not return a value


Simulation macro reference

This component does not contain any simulation macros


Property reference

TX Pin

This property is of type Single digital pin and can be referenced with the variable name TXPIN.

No additional information


RX Pin

This property is of type Single digital pin and can be referenced with the variable name RXPIN.

No additional information


Injector

This property is of type Fixed list of ints and can be referenced with the variable name Injector.

No additional information